臨淄化工廠10KV電纜故障查找
測試地點:臨淄            測試日期:2018-06-28     
電纜類別:10KV全塑電纜3×95

 
1、10kV 3X95銅芯全塑電纜,長度170米左右,直埋,路徑清楚,運行10余年,有中間頭,在引下附近,第一段由電線桿引下直埋至配電柜。
2、在配電室站側用搖表測量電纜絕緣電阻,黃相對地為0.6MΩ,其余兩相為紅地6MΩ,綠地200MΩ,相間測試紅綠200MΩ  黃綠200MΩ   紅黃6MΩ.
3、用低壓脈沖定位,波形比較,電纜全長為/168米。

  
                                   


根據測試情況選擇黃地打壓,升高電壓至20KV時擊穿放電,用脈沖電流測得故障位置在144米左右。距離對端比較近。


                                 

周期放電去聲磁定位,剛開始還能聽到聲音,在精確定位時發現聽不到聲音了,判斷為故障點燒穿,成為低阻故障,所以聲音減小,現場人員告知此處有一接頭,停止放電挖出接頭后發現接頭外觀完好,反復搖晃電纜接頭,繼續打壓,在接頭處聽到微弱放電聲,打開接頭后發現接頭進水。

                                        


                              